Prototipe Sistem Pengoperasian Gardu Portal Konvensional 20kv Dalam Kondisi Pemeliharaan

Putra, Robyaziz Versiwimpi (2017) Prototipe Sistem Pengoperasian Gardu Portal Konvensional 20kv Dalam Kondisi Pemeliharaan. Diploma thesis, Institut teknologi Sepuluh Nopember.

[thumbnail of 2214038010-Non_ Degree.pdf]
Preview
Text
2214038010-Non_ Degree.pdf - Published Version

Download (4MB) | Preview

Abstract

Berdasarkan data dilapangan bahwa masih banyaknya gardu portal konvensional untuk pelanggan tegangan menengah yang belum terdapat sistem pengaman dalam pengoperasiannya. Bilamana terjadi kesalahan operasi maka akan menyebabkan gangguan dan kegagalan sistem kerja pada jaringan PLN serta beresiko bahaya bagi operator pemelihara. Maka timbul ide mengenai penelitian tugas akhir ini membahas mengenai prototipe sistem pengoperasian gardu portal konvensional 20kV dalam kondisi pemeliharaan.
Sistem pengoperasian ini menggunakan magnetic kontaktor sebagai sistem interlock agar pengoperasian buka tutup LBS (Load Breaker Switch) pada jaringan satu fasa sesuai dengan SOP yang ada pada PLN. Sistem interlock ini dapat dilihat dengan lampu indikator. Lampu indikator ini sebagai penanda buka tutupnya LBS pada gardu konvensional. Pengiriman sinyal kondisi pengoperasian gardu, dengan menggunakan sensor peak detector sebagai pendeteksi operasi dari masing-masing section LBS yaitu membaca tegangan pada coil relay. Pengiriman sinyal ini dikirim melalui mikrokontroler. Hasil sistem pengoperasian dapat dilihat pada layar LCD panel box yaitu berupa kondisi dari gardu portal tersebut.
Sehingga sistem interlock pada magnetic kontaktor yang bekerja pada tegangan rata-rata yaitu sebesar 225,23 Volt dapat menjaga pengoperasian agar sesuai dengan SOP yang berlaku serta pembacaan sensor peak detector > 1,8 VDC menunjukkan bahwa kondisi saklar terbuka sebagai notifikasi untuk operator pemelihara dalam mengetahui kondisi saklar gardu portal konvensional.
==================================================================
Based on the data field that there are still many conventional portal substations for medium voltage customers who have no security system in operation. In the event of a fault of operation it will cause interference and failure of the working system on the PLN network and at risk of danger to the operator. Then the idea arose about this final project discuss about prototype of system operation of conventional portal 20kV in the condition of maintenance condition.
This operating system uses a magnetic contactor as an interlock system for the operation of open LBS (Load Breaker Switch) cover on a single phase network in accordance with the existing SOP in PLN. This interlock system can be viewed with indicator light. This indicator lamp as LBS open lid marker on conventional substation. Delivery signal condition of substation operation, using peak detector sensor as detection operation from each section LBS that is reading of stress on coil relay. This sending signal is sent through microcontroller. The results of the operating system can be seen on the LCD panel panel display is a condition of the substation portal.
So that the interlock system on the magnetic contactor working on the average voltage of 225.23 Volt can maintain the operation to comply with the applicable SOP as well as the readings of the sensor peak detector> 1.8 VDC indicates that the switch condition is open as a notification for the carrier in knowing Condition of conventional portal substation.

Item Type: Thesis (Diploma)
Uncontrolled Keywords: Gardu Konvensional, Magnetik Kontaktor, Sensor Peak Detector, Mikrokontroller, Conventional Substation, Magnetic Contactor, Peak Detector Sensor, Microcontroller
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission
Divisions: Faculty of Vocational > 36304-Automation Electronic Engineering
Depositing User: Robyaziz Versiwimpi Putra
Date Deposited: 19 Oct 2017 01:31
Last Modified: 06 Mar 2019 02:36
URI: http://repository.its.ac.id/id/eprint/47563