Nayahannah, Pugeh Aditya (2018) Analisis Pengaruh Perubahan Temperatur Terhadap Tegangan Tembus Pada Isolasi Minyak Transformator Jenis Mineral, Sintesis, Dan Nabati. Undergraduate thesis, Institut Teknology Sepuluh Nopember.
Preview |
Text
07111645000016-Undergraduate_Theses.pdf - Accepted Version Download (4MB) | Preview |
Abstract
Minyak transformator adalah salah satu jenis media isolasi yang berfungsi memisahkan antara bagian yang bertegangan maupun tidak bertegangan pada transformator. Selain itu, minyak transformator dapat difungsikan sebagai media pendingin. Salah satu faktor yang mempengaruhi kualitas isolasi dari minyak transformator adalah pengaruh perubahan temperatur yang disebabkan oleh ketidakseimbangan beban, beban berlebih, dan rugi-rugi yang terjadi pada inti transformator. Transformator dengan kualitas isolasi yang buruk berpotensi menyebabkan beberapa kerugian, diantaranya adanya pemadaman atau bahkan kerusakan serius pada transformator. Oleh karena itu, untuk mengamati kualitas isolasi minyak transformator, dilakukan pengujian pengaruh perubahan temperatur terhadap tegangan tembus minyak transformator. Minyak transformator yang digunakan sebagai obyek uji adalah jenis minyak yang sering digunakan sebagai media isolasi, yaitu minyak mineral, sintetis, dan nabati.
Pengujian dilakukan berdasarkan standar uji IEC 156 dengan menggunakan elektroda berbentuk jamur dengan jarak sela 2.5 mm. Sebelum diuji, sampel dilakukan pemanasan dengan kenaikan temperatur bertahap dengan lama pemanasan 30 menit. Setelah itu, dilakukan uji kadar air untuk mengetahui pengaruh kandungan air terhadap tegangan tembus yang diperoleh. Hasil pengujian menjelaskan bahwa kenaikan temperatur menyebabkan nilai tegangan tembus minyak semakin meningkat, akibat dari kandungan air yang semakin rendah. Minyak nabati memiliki nilai rata-rata tegangan tembus yang paling tinggi dibandingkan dengan minyak mineral dan sintetis sesuai dengan nilai titik nyala pada ketiga jenis minyak. ============ Transformer oil is one type of isolation media that serves to separate between the electricizied and non-electricizied part on the transformer. Furthermore, transformer oil has a function as a cooling medium. One of the factors affecting the insulating qualities of transformer oils is the effect of temperature changes caused by imbalance-load, overload, and losses occurring at the transformer core. Transformers with poor insulation quality have the potential to cause some losses, such as blackouts or even serious damage to the transformer. Therefore, in order to observe the quality of transformer oil insulation, the effect of temperature changes on transformer oil breakdown voltage was examined. The transformer oil used as a test object is a type of oil that often used as an insulating medium, such as mineral, synthetic, and vegetable oil.
The test was performed based on standard of IEC 156 by using mushroom-shaped electrodes with a gap of 2.5 mm. Prior to testing, the sample was heated with a gradual rise in temperature with a 30 minute heating time. After that, test the water content to determine the effect of water content to obtain the breakdown voltage. The test results explain that the rise in temperature causes the value of oil breakdown voltage increases, caused by lower water content. Vegetable oil has highest average value of the breakdown voltage compared with mineral and synthetic oils in accordance with the flash point value in all three types of oil.
Item Type: | Thesis (Undergraduate) |
---|---|
Uncontrolled Keywords: | Tegangan tembus; media isolasi minyak; perubahan temperatur; kadar air; Breakdown voltage; insulation of transformer oil; temperature change. |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3401 Insulation and insulating materials |
Divisions: | Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Pugeh Aditya Nayahannah |
Date Deposited: | 18 Jul 2018 08:16 |
Last Modified: | 09 Mar 2021 05:17 |
URI: | http://repository.its.ac.id/id/eprint/52476 |