Pengaruh Polutan Fly Ash Terhadap Tegangan Flashover Pada Isolator Berbahan Dasar Keramik

Rheza, Muhammad Syah (2018) Pengaruh Polutan Fly Ash Terhadap Tegangan Flashover Pada Isolator Berbahan Dasar Keramik. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 2214100193-Undergraduate_Theses.pdf] Text
2214100193-Undergraduate_Theses.pdf - Published Version
Restricted to Repository staff only

Download (2MB) | Request a copy

Abstract

Isolator jaringan tenaga listrik merupakan salah satu peralatan yang penting dalam jaringan tenaga listrik dimana isolator yang banyak digunakan di Indonesia adalah isolator keramik. Udara disekitar isolator yang dipasang pada ruangan terbuka dapat membawa polutan-polutan dan menempel pada permukaan isolator. Salah satu polutan yang dapat menempel adalah fly ash karena tidak semua polutan fly ash dapat tersaring sehingga dapat menempel pada isolator yang berada di sekitarnya. Oleh sebab itu, maka akan dilakukan studi mengenai pengaruh polutan fly ash terhadap arus bocor dan tegangan flashover pada isolator keramik. Pengujian arus bocor akan dilakukan dengan menggunakan metode step voltage sedangkan pengujian tegangan flashover akan dilakukan dengan metode ASTM D-149. Arus bocor yang didapatkan pada saat tegangan 5 kV pada isolator kering tanpa polutan adalah sebesar 3.59 mA, sedangkan pada saat diberi polutan fly ash 100 gram (NSDD = 0,0445 gr/cm2) maka arus bocor naik menjadi 4.53 mA dan pada saat diberi polutan fly ash 100 gram (NSDD = 0,0445 gr/cm2) dalam kondisi isolator basah, arus bocor naik menjadi 6.48 mA. Pada pengujian tegangan flashover, flashover hanya terjadi pada kondisi isolator basah berpolutan karena keterbatasan alat yang digunakan. Pada saat isolator basah dengan polutan 100 gram (NSDD = 0,0445 gr/cm2) tegangan flashover terjadi saat tegangan 55.53 kV, sedangkan pada isolator basah dengan polutan 300 gram (NSDD = 0,1335 gr/cm2) tegangan flashover terjadi saat tegangan 50.21kV. Dari pengujian yang telah dilakukan dapat ditarik kesimpulan bahwa dengan adanya polutan fly ash dapat menurunkan kinerja isolator ditinjau dari arus bocor dan tegangan flashover isolator. ============== Electrical power network insulators are one of the most important equipments in the power grid. The most popular insulator used in Indonesia is ceramic insulator. In the open air, insulator can be attached by pollutans. One of the pollutants that can be attached is fly ash. Not all fly ash pollutants can be filtered so they can stick to the surrounding insulators. Therefore, there will be a study of fly ash pollutants against leakage current and ceramic isolator flashover voltage. The leakage current test will be done using step voltage method while the flashover test will be done using ASTM D-149 method. The leakage current obtained at 5 kV at dry insulatorr without pollutant is 3.59 mA, while at 100 gram (NSDD = 0.0445 gr / cm2) fly ash pollutant then leaking current rises to 4.53 mA and when given 100 gram fly ash pollutant (NSDD = 0.0445 gr / cm2) in wet conditions, the leakage current rose to 6.48 mA. Flashover only occurs on the condition of wet pollutant insulator because of the limitations of the equiments. At the time of wet isolator with pollutant 200 gram (NSDD = 0,0890 gr / cm2) the flashover voltage occurred at 55,53 kV and at wet insulator with 300 grams pollutant (NSDD = 0.1335 gr / cm2) flashover voltage that occurs when the voltage is 50.21kV. From the test can be concluded that with the existence of fly ash pollutant that can decrease insulator performance and flashover isolator voltage.

Item Type: Thesis (Undergraduate)
Additional Information: RSE 621.319 5 Rhe p-1
Uncontrolled Keywords: Arus Bocor, Fly Ash, Isolator Keramik, NSDD, Tegangan Flashover, Ceramic Insulator, Flashover Voltage,Fly Ash, Leakage Current
Subjects: T Technology > TD Environmental technology. Sanitary engineering > TD427.F58 Fly ash
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3401 Insulation and insulating materials
T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK531 Current and voltage waveforms
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Muhammad Syah Rheza
Date Deposited: 22 Nov 2018 05:11
Last Modified: 22 Nov 2018 05:11
URI: http://repository.its.ac.id/id/eprint/53015