Monitoring Dan Analisis Dampak Pembebanan Terhadap Posisi Peletakan Sensor Vibrasi Pada Tangki Transformator Distribusi 20 kV

Anwar, Tauruski Syaifullah (2019) Monitoring Dan Analisis Dampak Pembebanan Terhadap Posisi Peletakan Sensor Vibrasi Pada Tangki Transformator Distribusi 20 kV. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111650010003-Master_Thesis.pdf]
Preview
Text
07111650010003-Master_Thesis.pdf - Accepted Version

Download (2MB) | Preview

Abstract

Transformator distribusi adalah salah satu peralatan yang sangat penting pada sistem tenaga [1]. Vibrasi adalah salah satu peristiwa besar pada transformator yang memulai setelah dekompresi (pengurangan) pada magnet core dan winding [2]. Monitoring vibrasi pada tangki transformator adalah cara yang paling efektif guna merepresentasikan vibrasi yang terjadi pada bagian dalam transformator [3].
Dari sekian penelitian terkait vibrasi pada tangki transformator hanya transformator daya yang banyak diujikan dan beberapa dilakukan pada uji laboratorium. Perlu adanya kajian lebih lanjut untuk dapat diterapkan pada transformator distribusi serta penggunaan sensor vibrasi yang dapat diimplementasikan pada tangki transformator distribusi.
Oleh sebab itu penelitian selanjutnya yakni monitoring dan analisis dampak pembebanan terhadap posisi peletakan sensor vibrasi pada tangki transformator distribusi 20 kV dengan mengimplementasikan elemen piezoelectric 20 mm sebagai tranduser vibrasi dengan rata – rata % error pengukuran ± 17,8 % dari desain yang telah dibuat.
Hasil eksperimen menunjukkan semakin meningkatnya pembebanan, maka vibrasi juga akan mengalami peningkatan sesuai dengan vibrasi yang terukur pada masing – masing sensor vibrasi. Sensor vibrasi yang terletak di 1/3 bagian atas (A0, A3, A6) dan 1/3 bagian bawah (A2, A5, A8) yang masing – masing memiliki nilai koefisien korelasi positif kuat lebih sensitif terhadap kenaikan pembebanan dari pada di 1/3 bagian tengah (A1, A4, A5) dengan nilai koefisien korelasi cukup/lemah dan sensor vibrasi yang terletak di 1/3 bagian bawah (A2, A5, A8) memiliki nilai vibrasi yang lebih tinggi dari keseluruhan peletakan sensor vibrasi
===============================================================================================
Distribution transformers are one of the most important equipment in the power system [1]. Vibration is one of the major events in the transformer that starts after decompression (reduction) on the magnetic core and winding [2]. Vibration monitoring in a transformer tank is the most effective way to represent vibrations that occur on the inside of the transformer [3].
Of the various studies related to the vibrations in the transformer tank, only power transformers are tested and some are carried out in laboratory tests.Further studies are needed to be applied to distribution transformers and the use of vibration sensors that can be implemented in distribution transformers.
Therefore the next study is impact monitoring and analysis of loading on the position of the vibration sensor placement in a 20 kV distribution transformer tank by implementing a 20 mm piezoelectric element as a vibrational transducer with an average% measurement error ± 17.8% of the design made.
The experimental results show that the higher the load, the vibration will also increase according to the vibrations measured on each vibration sensor.Vibration sensors located in the 1/3 upper part (A0, A3, A6) and 1/3 lower part (A2, A5, A8) which each have a strong positive correlation coefficient are more sensitive to the increase in loading than at 1 / 3 the middle part (A1, A4, A5) with a sufficient / weak correlation coefficient and vibration sensor located in the 1/3 lower part (A2, A5, A8) has a higher vibration value than the overall vibration sensor placement.

Item Type: Thesis (Undergraduate)
Additional Information: RTE 621.314 Anw m-1 2019
Uncontrolled Keywords: Piezoelectric, Transformator distribusi, Vibrasi, Korelasi pearson
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering
Divisions: Faculty of Electrical Technology > Electrical Engineering > 20101-(S2) Master Thesis
Depositing User: tauruski .
Date Deposited: 02 Jun 2021 08:03
Last Modified: 06 Aug 2021 07:03
URI: http://repository.its.ac.id/id/eprint/60226

Actions (login required)

View Item View Item