Widiyaningtias, Sri Wahyuni (2019) STUDI NUMERIK MODIFIKASI PEMBANGKIT SIKLUS GANDA KOGENERASI MENGGUNAKAN SOFTWARE CYCLE TEMPO 5.0. Other thesis, INSTITUT TEKNOLOGI SEPULUH NOPEMBER.
|
Text
02111540000091_Undergraduate_thesis.pdf Restricted to Repository staff only Download (3MB) | Request a copy |
Abstract
Salah satu industri yang banyak menerapkan sistem kogenerasi adalah industri makanan seperti PT. Ajinomoto Indonesia (PT AI) yang berlokasi di kabupaten Mojokerto. Pembangkit kogenerasi yang terdapat di PT AI yaitu pembangkit listrik tenaga gas uap (PLTGU) yang memproduksi listrik sebesar 12 MW dan uap sebesar 55 Ton/h. Setelah uap keluar dari steam turbin maka uap digabung dengan uap yang dihasilkan oleh 3 Coal boiler untuk memenuhi kebutuhan uap dalam proses industri sebesar 100 Ton/h. Sistem pembangkit kogenerasi di PT AI telah tercover dengan aplikasi bawaan design dan dari awal pengoperasian hingga saat ini aplikasi tersebut belum di kalibrasi sehingga memungkinkan hasil yang ditampilkan kurang valid. Selain itu, Pembangkit kogenerasi yang terdapat di PT AI belum pernah dilakukan modifikasi untuk mendapatkan efisiensi pembangkit yang lebih tinggi. Artinya pembangkit kogenerasi di PT AI masih dalam keadaan seperti saat awal pengoperasian. Oleh sebab itu maka perlu dilakukan perhitungan ulang efisiensi pembangkit kogenerasi serta melakukan modifikasi pembangkit kogenerasi di PT AI menggunakan Software Cycle Tempo. Hal ini dikarenakan perhitungan dan modifikasi menggunakan Software Cycle Tempo dinilai lebih mudah dan efektif.
Penelitian tugas akhir ini mengenai studi numerik pembangkit kogenerasi di PT AI yang dimodifikasi dengan tiga pemodelan menggunakan Software Cycle Tempo 5.0. Penelitian ini dilakukan dengan beberapa tahapan dalam memecahkan masalah dan melakukan proses analisis. Pada tahapan awal dilakukan identifikasi masalah dengan melakukan studi lapangan di PT AI. Dari masalah yang didapat kemudian dilakukan simulasi pemodelan pembangkit dalam kondisi existing. Setelah itu, dilakukan simulasi tiga pemodelan pembangkit dalam kondisi yang telah dimodifikasi yaitu pada pemodelan pertama modifikasi dilakukan dengan menghilangkan komponen coal boiler, pemodelan kedua modifikasi dilakukan dengan menambahkan preheater dan pemodelan ketiga modifikasi dilakukan dengan mengganti komponen superheater 1 menjadi reheater. Dari masing-masing pemodelan didapatkan hasil berupa nett power, dan masukan kalor. Hasil dari pemodelan dalam kondisi existing dan sesudah dimodifikasi ini kemudian diolah untuk mendapatkan nilai efisiensi pembangkit dari masing-masing pemodelan yang selanjutnya dibandingkan dan dilakukan analisa.
Berdasarkan simulasi Software Cycle Tempo yang dilakukan pada laju aliran massa uap yang sama untuk proses industri, didapatkan hasil yaitu pada pembangkit kogenerasi PT AI pada kondisi existing memiliki nilai efisiensi sebesar 69,34%. Pembangkit kogenerasi PT AI pada kondisi modifikasi tanpa coal boiler (secara teoritis) memiliki nilai efisiensi sebesar 87,44%. Pembangkit kogenerasi PT AI pada kondisi modifikasi dengan penambahan komponen preheater memiliki nilai efisiensi sebesar 69,36%. Pembangkit kogenerasi PT AI pada kondisi modifikasi dengan penggantian komponen superheater 1 menjadi reheater memiliki nilai efisiensi yang lebih tinggi dibandingkan dengan pembangkit pada kondisi existing yaitu sebesar 70,18%.
====================================================================================================================================
One of industries that has a lot of cogeneration systems is the food industry such as PT. Ajinomoto Indonesia (PT AI) located in Mojokerto district. The cogeneration plant in PT AI is a steam gas power plant (PLTGU) that produces 12 MW of electricity and steam 55 tons/h. After the steam comes out of the steam turbine, it is combined with the steam produced by 3 Coal boilers to meet the steam needs in industrial processes of 100 Ton/h. The cogeneration system at PT AI has been covered with the default application design and from the beginning of the operation till now the application has not been calibrated thus the results shown to be less valid. In addition, the cogeneration plant found at PT AI has never been modified to obtain higher plant efficiency. It means that the cogeneration plant at PT AI is still in the same condition as the initial operation. Therefore, it is necessary to recalculate the efficiency of the cogeneration generator and modify the cogeneration plant at PT AI using the Software Cycle Tempo. It is because the calculation and modification using Software Cycle Tempo is considered easier and more effective.
The research of this study is about the numerical study of cogeneration plant in PT AI which is modified by three modeling using Cycle Tempo 5.0 Software. This research was carried out with several stages in problems solving and the analytical process. In the early stage, identification of problems was carried out by conducting field studies at PT AI. From the problems obtained, the plant modeling simulation is then carried out in existing conditions. After that, three plant modeling simulations were implemented in modified conditions, namely in the first modification model done by removing the coal boiler component, the second modeling modification was done by adding a preheater and the third modeling modification was done by replacing the superheater 1 component into a reheater. From each modeling the results are in the form of nett power, and heat input. The results of the modeling in the existing and after modification conditions are then processed to obtain system efficiency values from each model which is then compared and analyzed.
Based on the Software Cycle Tempo simulation, the results obtained are that the existing PT AI cogeneration plant has an efficiency value of 69,34%. The cogeneration plant of PT AI under modified conditions without coal boiler has an efficiency value of 87,44%. The PT AI cogeneration plant under the conditions of modification with the addition of the preheater component has an efficiency value of 69,36%. The PT AI cogeneration plant in a modified condition by replacing the superheater 1 component into a reheater has a higher efficiency value compared to the plant in the existing condition which is 70,18%.
| Item Type: | Thesis (Other) |
|---|---|
| Subjects: | T Technology > TJ Mechanical engineering and machinery > TJ164 Power plants--Design and construction |
| Divisions: | Faculty of Industrial Technology > Mechanical Engineering > 21201-(S1) Undergraduate Thesis |
| Depositing User: | SRI WAHYUNI WIDIYANINGTIAS |
| Date Deposited: | 21 Jul 2026 01:19 |
| Last Modified: | 21 Jul 2026 01:19 |
| URI: | http://repository.its.ac.id/id/eprint/66536 |