Setiawan, Arif (2015) Koordinasi Proteksi Adaptif Rele Arus Lebih Digital Menggunakan Algoritma Genetika Pada Jaringan Distribusi Radial Dengan Pembangkit Tersebar. Undergraduate thesis, Institut Technology Sepuluh Nopember.
Preview |
Text
2213105023-Undergraduate Thesis.pdf - Published Version Download (2MB) | Preview |
Abstract
Suatu pembangkit tersebar, bila dipasang pada jaringan
distribusi radial, akan menyebabkan berubahnya karakteristik umum
dari jaringan distribusi radial. Salah satu perubahan karakteristik itu
adalah koordinasi proteksi pada jaringan tersebut. Besar arus kontribusi
akan bertambah besar seiring pertambahan pembangkit tersebar serta
aliran arus kontribusi juga mengalir dua arah sehingga perlu adanya
peralatan proteksi yang bisa mendeteksi dua arah arus ganggunan.
Disamping itu pengoperasian pembangkit tersebar dapat bersifat on atau
off , sehingga hal tersebut dapat menghasilkan kemungkinan perubahan
konfigurasi yang berubah-ubah. Skema koordinasi adaptif diterapkan
agar tercipta koordinasi pengaman yang optimal dengan menerapkan
koordinasi yang berbeda pada tiap konfigurasi. Pada simulasi digunakan
jaringan distribusi radial 5 bus yang terhubung dengan pembangkit
tersebar pada bus 5 dan bus 2. Koordinasi adaptif memanfaatkan sebuah
peralatan rele arus lebih digital agar dapat berkomunikasi dengan pusat
kontrol otomatis . Algoritma genetika digunakan dalam koordinasi antar
rele berupa time dial dan arus pickup sehingga dapat menghasilkan
setelan yang tepat. Dari hasil simulasi dihasilkan peningkatan
sensitivitas dan kecepatan ketika sistem adaptif diterapkan pada
jaringan
======================================================================================================
Injection distributed generator on radial distribution system
caused a general characteristic of radial distribution system changed.
One of changes in the characteristics is protection coordination on the
network. The current magnitude will increase and current flow will
contributes bidirectionally so that bidirectional apparatus protection
capability is needed such as directional over current relay. Beside that,
distributed generator operation has some condition like on or off status.
Therefore it can generate possible changes in the configuration.
Adaptive coordination scheme can be implemented in order to get
optimal coordination by using different coordination based on
configuration. Radial distribution system connected distributed
generator on bus 5 and bus 2 implemented on this simulation. Digital
over current relay is used in order to the relay can communicate with
automatic control center. Genetic algorithm can be applied on system
that aim to get correct time dial and pickup current. The Simulation
results more sensitive and faster coordination when adaptive system
applied on network.
Item Type: | Thesis (Undergraduate) |
---|---|
Additional Information: | RSE 621.319 Set k |
Uncontrolled Keywords: | Sistem distribusi radial, pembangkit tersebar, rele digital, koordinasi proteksi adaptif , algoritma genetika |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK201 Electric Power Transmission Q Science > QA Mathematics > QA402.5 Genetic algorithms. Interior-point methods. |
Divisions: | Faculty of Industrial Technology > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Mr. Tondo Indra Nyata |
Date Deposited: | 30 Oct 2019 07:24 |
Last Modified: | 30 Oct 2019 07:24 |
URI: | http://repository.its.ac.id/id/eprint/71507 |
Actions (login required)
View Item |