Soebagio, Juan Christian (2020) Karakteristik Pola Partial Discharge Inception Voltage Menggunakan Antena Pada Isolasi Udara. Undergraduate thesis, Institut Teknologi Sepuluh Nopember.
Preview |
Text
07111640000008-Undergraduate_Thesis.pdf Download (2MB) | Preview |
Abstract
Peralatan tegangan tinggi dapat rusak saat terjadi kegagalan pada isolasi. Kegagalan akan ditandai dengan adanya fenomena Partial Discharge (PD) saat kondisi pre-breakdown. Metode deteksi PD yang umum digunakan seperti thermografi dan acoustic emission (AE) masih memiliki beberapa kelemahan. Berdasarkan kondisi tersebut studi ini membahas metode deteksi PD yang mengandung Ultra High Frequency (UHF) pada isolasi udara dengan menggunakan antena yang dapat menangkap gelombang elektromagnetik. Elektroda yang digunakan adalah needle to plane (jarum ke datar). Variabel yang digunakan adalah bentuk dan jarak elektroda. Karakteristik yang dianalisa pada saat partial discharge inception voltage (PDIV). Data yang diambil akan diolah dengan Phase Resolved Partial Discharge (PRPD). Hasil analisa yang didapatkan dari antena akan dibandingkan dengan metode leakage current dengan menggunakan High Frequency Current Transformer (HFCT). Hasil pengujian ini menunjukkan bahwa pola PDIV dapat diamati pada analisa PRPD, setiap elektroda memiliki karakteristik PD pada sudut fasa tertentu, elektroda runcing PD dominan terjadi pada sudut 331.2° hingga 342°, elektroda kotak PD dominan terjadi pada sudut 334.8° hingga 356.4°, dan elektroda tumpul PD dominan terjadi pada sudut 306° hingga 313.2°. Sehingga dapat disimpulkan bahwa antena loop dapat digunakan untuk mendeteksi dan mengamati pola PDIV pada isolasi udara.
======================================================================================================================
High voltage equipment can be damaged when there is a failure of the insulation. Failure will be marked by the Partial Discharge (PD) phenomenon during the pre-breakdown condition. PD detection methods commonly used such as thermography and acoustic emission (AE) still have some weaknesses. Based on these conditions, this study discusses the detection method of PD containing Ultra High Frequency (UHF) in air insulation using an antenna that can capture electromagnetic waves. The electrodes used are needle to plane. The variables used are the shape and distance of the electrode. Characteristics analyzed during partial discharge inception voltage (PDIV). The data retrieved will be processed so that it displays Phase Resolved Partial Discharge (PRPD). The results obtained from the antenna will be compared with the leakage current method using the High Frequency Current Transformer (HFCT). PDIV pattern can be observed in the PRPD analysis, each electrode has the characteristics of PD at a certain phase angle. The dominant PD point electrodes occur at an angle of 331.2 ° to 342 °, the dominant PD box electrodes occur at an angle of 334.8 ° to 356.4 °, and the dominant PD blunt electrode occurs at an angle of 306 ° to 313.2 °. So, it can be concluded that the loop antenna can be used to detect and observe PDIV patterns in air insulation.
Item Type: | Thesis (Undergraduate) |
---|---|
Uncontrolled Keywords: | Partial Discharge, Loop Antenna, Needle to plane variation, Partial Discharge, Antena Loop, Variasi jarum-plat. |
Subjects: | T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK452 Electric apparatus and materials |
Divisions: | Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis |
Depositing User: | Juan Christian Soebagio |
Date Deposited: | 07 Aug 2020 03:04 |
Last Modified: | 17 May 2023 04:39 |
URI: | http://repository.its.ac.id/id/eprint/77154 |
Actions (login required)
View Item |