Analisa Gangguan Short Circuit serta Pengaturan Koordinasi Proteksi pada Container Crane Disuplai dengan Energi Terbarukan Berbasis Simulasi

Priyangga, Sastri Ade (2020) Analisa Gangguan Short Circuit serta Pengaturan Koordinasi Proteksi pada Container Crane Disuplai dengan Energi Terbarukan Berbasis Simulasi. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 04211640000075_Undergraduate Thesis.pdf]
Preview
Text
04211640000075_Undergraduate Thesis.pdf

Download (3MB) | Preview

Abstract

Konsep pelabuhan ramah lingkungan atau dikenal dengan istilah green port kini diterapkan oleh seluruh negara-negara di ASEAN yang bertujuan untuk mengurangi tingkat pencemaran laut, polusi udara serta berbagai dampak kerusakan lingkungan yang ditimbulkan oleh berbagai aktifitas bongkar muat di pelabuhan. Salah satu upaya dalam mewujudkan konsep green port yang diaplikasikan pada container crane adalah konsep elektrifikasi, yaitu menggunakan sumber energi listrik yang sebelumnya menggunakan bahan bakar fosil dialihkan dengan energi terbarukan. Kondisi di lapangan yang tidak menentu sesuai dengan faktor lingkungan yang terlibat dapat menyebabkan suatu sistem mengalami kegagalan. Short circuit adalah hubungan yang disengaja antara konduksi melalui hambatan atau impedansi yang memiliki perbedaan yang cukup potensial. Gangguan short circuit terjadi ketika konduktor yang memiliki tegangan yang terhubung ke konduktor tegangan lain atau terhubung langsung ke konduktor yang bersifat netral (ground). Oleh sebab itu diperlukan adanya sistem koordinasi proteksi untuk meminimalisir adanya gangguan pada sistem kelistrikan, salah satunya dengan menggunakan circuit breaker. Pada penelitian ini dilakukan simulasi menggunakan software ETAP untuk mengetahui besar arus dari gangguan short circuit dan perencanaan sistem koordinasi proteksi setiap circuit breaker pada komponen yang membutuhkan daya besar dengan arus hubungan singkat maksimal yaitu 9,882 kA pada motor hoist, 3,586 kA pada motor boom, 1,683 kA pada motor trolley dan 4,415 kA pada motor gantry dengan keseluruhan disuplai dengan energi terbarukan. Pengujian ini dilakukan pada beberapa konfigurasi suplai daya dan variasi skema operasi dari motor utama. Diharapkan juga nantinya akan menghasilkan solusi untuk pengaturan sistem koordinasi proteksi circuit breaker pada container crane.
========================================================================================================================
The concept of an environmentally friendly port or also known as a green port is now being applied by all countries in ASEAN which aims to reduce levels of marine pollution, air pollution, and various environmental impacts caused by various loading and unloading activities at ports. One effort to realize the green port concept that is applied to container cranes is the concept of electrification, which uses electrical energy sources that previously used fossil fuels to be transferred to renewable energy. Conditions in the field that are not certain according to the environmental factors involved can cause a system to fail. A short circuit is an intentional connection between conduction via resistance or impedance that has a considerable potential difference. A Short circuit occurs when a conductor that has a voltage is connected to a conductor of another voltage or is directly connected to a conductor that is neutral (ground). Therefore, it is necessary to have a protection coordination system to minimize any disturbances in the electrical system, one of which is by using a circuit breaker. In this study, a simulation using ETAP software was carried out to determine the current magnitude of short circuit disturbances and the planning of the protection coordination system for each circuit breaker on components that require large power with a maximum short circuit current of 9.882 kA on the motor hoist, 3.586 kA on the motor boom, 1.683 kA on the motor trolley, and 4.415 kA on the motor gantry, which those are entirely supplied with renewable energy. This test is carried out on several power supply configurations and various operating schemes of the main motor. It is also hoped that later it will solve setting up a circuit breaker protection coordination system on the container crane.

Item Type: Thesis (Other)
Uncontrolled Keywords: Green port, Container crane, Short Circuit, Circuit Breaker, ETAP.
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2861 Electric relays
V Naval Science > V Naval Science (General)
Divisions: Faculty of Marine Technology (MARTECH) > Marine Engineering > 36202-(S1) Undergraduate Thesis
Depositing User: Sastri Ade Priyangga
Date Deposited: 27 Aug 2020 01:09
Last Modified: 22 Jun 2023 14:19
URI: http://repository.its.ac.id/id/eprint/79953

Actions (login required)

View Item View Item