Evaluasi Sistem Koordinasi Proteksi Pembangkit Listrik Tenaga Uap ST 2.0 Grati POMU

Asadulloh, Latief Ni'am (2023) Evaluasi Sistem Koordinasi Proteksi Pembangkit Listrik Tenaga Uap ST 2.0 Grati POMU. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111840000031-Undergraduate_Thesis.pdf] Text
07111840000031-Undergraduate_Thesis.pdf - Accepted Version
Restricted to Repository staff only until 1 April 2025.

Download (2MB) | Request a copy

Abstract

Evaluasi sistem proteksi generator merupakan salah satu cara untuk mencegah terjadinya kerusakan pada generator. Penelitian ini membahas topik evaluasi sistem proteksi generator ST 2.0 Grati POMU yang berguna untuk meningkatkan kehandalan sistem proteksi dalam mengamankan generator dari gangguan yang mungkin terjadi. Penelitian ini berfokus pada empat relai yang ada pada generator, antaranya: relai eksitasi lebih (ANSI 24), relai hilang medan (ANSI 40), relai arus lebih dengan kendali tegangan (ANSI 51V), dan relai differensial generator (87G). Evaluasi sistem proteksi generator didasarkan pada standart IEEE dan perhitungan atas setting yang disesuaikan dengan manualbook dari generator ST 2.0 Grati POMU. Aplikasi Etap 12.6 merupakan aplikasi yang digunakan pada penelitian ini untuk melakukan simulasi sistem kelistrikan Grati POMU. Hasil dari Tugas Akhir ini didapatkan bahwa setting pada relai eksitasi lebih (ANSI 24), relai hilang medan (ANSI 40), dan relai arus lebih dengan kendali tegangan (ANSI 51V) perlu dilakukan resetting. Pada relai eksitasi lebih (ANSI 24), Trip stage di resetting dari yang semula 1.4 dengan time delay sebesar 0.8 detik dibuah menjadi 1.2 dengan time delay 2 detik. Pada relai hilang medan (ANSI 40), Kurva CH1 berubah menjadi 0.55 (dalam Q p.u) dengan sudut 77°. Kemudian pada relai 51V nilai Ip (arus pick-up) diubah menjadi 1.1 dari FLA generator dengan voltage restrain sebesar 75 V. Evaluasi sistem proteksi generator dapat menjadi rekomendasi untuk Grati POMU serta berbagai instansi guna mengatur sistem proteksi generatornya
========================================================================================================================================
Evaluation of the generator protection system is one way to
prevent damage to the generator. This research discusses the topic of evaluating the ST 2.0 Grati POMU generator protection system which is useful for improving the reliability of the protection system in securing the generator from disturbances that may occur. This research focuses on four relays on the generator, including: over excitation relay (ANSI 24), field loss relay (ANSI 40), overcurrent relay with voltage control (ANSI 51V), and generator differential relay (87G). Evaluation of the generator protection system is based on IEEE standards and calculations of settings adjusted to the manualbook of the ST 2.0 Grati POMU generator. The Etap 12.6 application is the application used in this study to simulate the Grati POMU electrical system. The results of this Final Project found that the settings on the over-excitation relay (ANSI 24), lost field relay (ANSI 40), and overcurrent relay with voltage control (ANSI 51V) need to be reset. In the over-excitation relay (ANSI 24), the Trip stage is resetting from the original 1.4 with a time delay of 0.8 seconds to 1.2 with a time delay of 2 seconds. At the field loss relay (ANSI 40), the CH1 curve changes to 0.55 (in Q p.u) with an angle of 77°. Then at the 51V relay, the Ip (pick-up current) value was changed to 1.1 of the generator FLA with a voltage restrain of 75 V. Evaluation of the generator protection system can be a recommendation for Grati POMU and various agencies to regulate the generator protection system.

Item Type: Thesis (Other)
Uncontrolled Keywords: Pembangkit Listrik, Gangguan, Evaluasi Sistem Proteksi Generator, Resetting Relai Power Plant, Disturbance, Generator Protection System Evaluation, Relay Resetting.
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK1001 Production of electric energy or power
Divisions: Faculty of Intelligent Electrical and Informatics Technology (ELECTICS) > Electrical Engineering > 20201-(S1) Undergraduate Thesis
Depositing User: Latief Ni'am A
Date Deposited: 07 Feb 2023 03:40
Last Modified: 07 Feb 2023 03:40
URI: http://repository.its.ac.id/id/eprint/96277