Studi Komparasi Dan Pengujian Deteksi Peluahan Sebagian Pada Isolasi Minyak Dan Isolasi Udara Menggunakan Loop Antena

Bahy, Chairul (2022) Studi Komparasi Dan Pengujian Deteksi Peluahan Sebagian Pada Isolasi Minyak Dan Isolasi Udara Menggunakan Loop Antena. Other thesis, Institut Teknologi Sepuluh Nopember.

[thumbnail of 07111840000223-Undergraduate_Thesis.pdf] Text
07111840000223-Undergraduate_Thesis.pdf - Accepted Version

Download (5MB)

Abstract

Isolator adalah peralatan fundamental yang terdapat pada sistem tenaga listrik dan berfungsi sebagai pemisah antara dua atau lebih penghantar listrik yang bertegangan. Pemisahan tersebut memiliki tujuan untuk menghindari arc(percikan) atau lompatan listrik. Terdapat berbagai isolasi dalam yang umum digunakan pada peralatan tinggi seperti isolasi udara, minyak, dan air. Peralatan dapat mengalami kerusakan saat terjadi kegagalan breakdown isolasi karena pengaruh suhu, karbonisasi, dan munculnya arc. Peluahan sebagian adalah fenomena tegangan tinggi yang terjadi akibat pelepasan muatan listrik yang terjadi pada suatu bahan isolasi dan merupakan salah satu tanda penurunan kualitas isolasi. Pada tugas akhir ini akan membahas deteksi partial discharge pada isolasi minyak dan isolasi udara menggunakan loop antena. Pembangkitan tegangan tinggi AC akan dihubungkan dengan elektroda needle to plate dengan variasi jarak elektroda 1cm, 1,5cm, dan 2cm. Loop antenna akan dihubungkan dengan Osiloskop sehingga hasil sinyal dapat diubah kedalam nilai tegangan. Hasil sinyal tersebut akan diolah sehingga menampilkan Phase Resolved Partial Discharge (PRPD) dan divalidasi dengan sinyal yang ditangkap oleh High Frequency Current Transformer (HFCT). Pada deteksi partial discharge isolasi minyak, elektroda jarak 1 cm, 1,5 cm, dan 2 cm dideteksi jumlah titik PRPD sebanyak 119, 90, dan 85 secara berurutan.
===================================================================================================================================
An insulator is fundamental equipment in an electric power system and works as a separator between two or more voltage conductors. The separation has the aim of avoiding arcs or electric jumps. Various types of insulation are commonly used in high-rise equipment, such as air, oil and air insulation. Partial discharge can damage equipment during fault failure due to temperature, carbonization and arc formation. Partial discharge is a high-voltage phenomenon that occurs due to an electric charge on insulating material and is a sign of a decrease in the quality of the insulation. In this final project, partial discharge detection was used using insulating oil and air insulation with a loop antenna. The AC high voltage generator will install needle to plate electrodes with variations of 1cm, 1.5cm, and 2cm electrode distances. Loop antennas will be connected with an oscilloscope to convert the resulting signal into a voltage value. The resulting signal will be processed to display the Phase Resolved Partial Discharge (PRPD) and validated with the signal captured by the High-Frequency Current Transformer (HFCT). In the partial discharge of insulating oil, electrodes at a distance of 1 cm, 1.5 cm, and 2 cm detected the number of PRPD as much as 119, 90, and 85, respectively.

Item Type: Thesis (Other)
Additional Information: RSE 621.314 Bah s-1 2022
Uncontrolled Keywords: HFCT, Loop Antena, Partial Discharge, PRPD
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK3401 Insulation and insulating materials