Febrilian, Ratu Gengsar (2021) Evaluasi dan Rencan Perkuatan Struktur Gedung Hotel Shafira di Surabaya Menggunakan Breising Baja Aakibat Beban Gempa SNI 1726:2019 dan Persyaratan Beton Struktural SNI 2847:2019. Diploma thesis, Institut Teknologi Sepuluh Nopember.
Preview |
Text
10111710013004_Undergradute Thesis.pdf Download (19MB) | Preview |
Abstract
Hotel Shafira merupakan salah satu gedung dengan 10 lantai yang terletak di jalan Ahmad Yani, Surabaya. Gedung yang didesain dengan sistem ganda ini masih direncanakan dengan peraturan yang lama yaitu SNI 1726:2012. Sedangkan terdapat revisi peraturan terhadap SNI 1726:2012 yaitu SNI 1726:2019 tentang cara perencanaan ketahanan gempa untuk struktur bangunan gedung. Perubahan ini dikhawatirkan berakibat pada peningkatan beban gempa rencana dan peningkatan detail struktur. Secara teori, struktur gedung yang dirancang menggunakan SNI lama akan mengalami tegangan berlebih jika menerima beban gempa rencana menurut SNI terbaru (Sukrawa et al., 2016). Respon spektrum pastinya juga akan mengalami perubahan puncak. Dengan adanya perubahan nilai respon spektrum dapat mempengaruhi level kinerja dalam mengakomodasikan beban gempa yang bekerja (Farlianti & Sapta, 2020). Hal ini merupakan alasan perlunya dilakukan evaluasi pada sistem struktur bangunan yang telah ada.
Pada SNI 1726:2012 didapatkan parameter beban gempa Ss sebesar 0,65 dan S1 sebesar 0,28. Sedangkan, pada SNI 1726:2019 parameter percepatan gempa mengalami kenaikan yaitu Ss menjadi 0,7 dan S1 menjadi 0,3. Puncak percepatan spectra (Sa) juga menglami kenaikan dari 0,6 menjadi 0,65. Kemudian dilakukan analisis struktur pada gedung dan didapatkan hasil bahwa periode dan simpangan antar lantai tidak memnuhi. Hal ini menunjukkan bahwa gedung tidak kaku. Struktur bangunan dengan beban gempa juga tidak memenuhi SNI 1729:2019. Untuk memperbaiki kinerja struktur terhadap respon gempa, maka dilakukan perkuatan dengan menggunakan breising agar menambah kekauan pada bangunan.
Perkutan elemen struktur pada bangunan ini juga dilakukan. Didapati kapasitas joint balok kolom dan geser pada balok tidak memenuhi kapasitas yang dibutuhkan. Sehingga dilakukan perkuatan dengan kapital kolom untuk joint balok kolom yang tidak memenuhi dan perkuatan menggunakan Carbon Fiber Reinforced Polymer (CFRP) untuk kapasitas geser balok yang tidak memenuhi.
=====================================================================================================
Hotel Shafira is one of building consist of 10 floors, located in Jalan Ahmad Yani, Surabaya. This building is designed with dual system and using the old regulation which is SNI 1726:202. While there is revision for this regulation arranged in SNI 1726:2019 concern of design procedure of seismic load for structural building. This change could affect to increase seismic load and ductile. Theortically, structure building designed by old regulation will have more stress if take seismic load of new regulation (Sukrawa et al., 2016). Spectrum response definitely has different summit. As it changes will affect performance level in accommodation of seismic load. In this way, evaluation of this system structure is needed.
In SNI 1726:2012, the earthquake load parameter Ss and S1 are 0.65 and 0.28. Meanwhile, in SNI 1726:2019, the earthquake load parameter Ss and S1 are 0.7 and 0.3. As of, summit of accelerate earthquake is increase from 0.6 to 0.65. Then, analysized the structure and have result that periode and displacement stories are not accomplish. This means the building is not stiff. To improve the performance of structure for seismic load, than structure strengthened by bracing so it gets more stiffness.
Structure element strengthened for this building is done. It found that joint beam column capacity and beam shear capacity are not accomplish as need capacity. Structure element strengthened by column capital for unaccomplished beam-column joint and Carbon Fiber Reinforced Polymer (CFRP) for unaccomplished beam shear capacity.
Item Type: | Thesis (Diploma) |
---|---|
Uncontrolled Keywords: | Beban Gempa SNI 1726:2019, Evaluasi Struktur, Perkuatan Sistem Struktur, Perkuatan Elemen Struktur, Breising, Kapital Kolom, Carbon Fiber Reinforced Polymer. ======================================================================================================================== Seismic Load SNI 1726:2019, Structure Evaluation, Structural Retrofitting, Strengthening of Structural Elements, Bracing, Column Capital, Carbon Fiber Reinforced Polymer. |
Subjects: | T Technology > TA Engineering (General). Civil engineering (General) |