Abstract

Jaring Distribusi Radial adalah jaring yang paling banyak digunakan untuk distribusi listrik
karena arsitektur yang sederhana dan biaya investasi yang rendah. Pesatnya pertambahan
pelanggan mengakibatkan jaring distribusi menjadi tidak seimbang dan terdistorsi
harmonisa. Hal-hal ini menyebabkan jaring distribusi mengalami rugi-rugi daya yang
besar. Rugi-rugi daya dapat diatasi dengan pemasangan kompensator daya reaktif, namun,
kompensator daya reaktif ini harus dipasang secara benar untuk menghindari peningkatan
harmonisa melebihi standar IEEE 519-1992.
Oleh karena itu, pada makalah ini diusulkan Direct Search Algorithm (DSA) untuk
menyelesaikan penempatan kapasitor pada jaring distribusi tidak seimbang dan terdistorsi
harmonisa. Loss Sensitivity Factor (LSF) digunakan untuk menentukan calon lokasi
dengan pengurangan kerugian daya maksimum. Algoritma yang diusulkan telah diuji pada
sistem uji IEEE jaring distribusi radial 13 bus. Perbandingan kinerja DSA dilakukan
melalui pencarian penurunan rugi-rugi daya maksimum untuk tiga kasus yaitu tanpa
penempatan kapasitor, tanpa batasan THD dan dengan batasan THD. Hasil penelitian
menunjukkan bahwa strategi yang diusulkan pada kasus ketiga memberikan penghematan
lebih besar dari kasus-kasus lain. ========== Radial Distribution System is the most widely used system for power distribution because
it has simple architechture and low investment costs. In contrast, due to the addition of the
customers some challenges are rised about power system losses, unbalance issues and
spread of harmonics which are both single phase and three phase customers. The power
system losses can be overcome with the proper installation of reactive power compensator.
This reactive power compensator must be installed approriately to avoid the system
harmonic level exceeding the IEEE 519-1992 standard. Capacitor will be installed for
compensating reactive power to maintain the voltage profile of the system.
To overcome this problem, an effective algorithm is needed to identify the optimal location
and capacity of capacitor in this system. This study will use harmonic power flow for
distribution system. The load flow calculated voltage profile and harmonic distortion level
on each bus voltage. Direct Search Algorithm works with loss sensitivity factor to find the
most appropriate location and capacity of reactive power compensator without increasing
harmonic distortion on the system. By considering THD, the best and location and capacity
of reactive power compensator will be yielded while maintaining the voltage profile and
minimize the power system losses.

Item Type: Thesis (Masters)
Additional Information: RTE 621.313 Apr p
Uncontrolled Keywords: penempatan kapasitor, harmonic power flow, distribution power flow, direct search algorithm, Capacitor, Radial Distribution Power Flow, Harmonic Power Flow Algorithm, Direct Search Algorithm, Loss Sensitivity Factor
Subjects: T Technology > TK Electrical engineering. Electronics Nuclear engineering > TK2692 Inverters